SENSOR SETTING

— When choosing sensor, standard of sensor curve will be needed. If temperature sensor is set as
SGH (120ºC resistor type), sensor curve should be SGH (120
(120ºC resistor type), sensor curve should be SGD curve.
— If there is difference between standard sensor curve and chosen sensor curve, select "defined
sensor", and then input defined sensor curve.
— When sensor curve is inputted, X value (resistance) must be in accordance with the order of higher
to lower, otherwise errors will occur.
— When sensor is selected as "Not used", temperature, pressure and fuel level will be display as "- - -"
in LCD.
— If there is no pressure sensor, but only has low pressure alarm switch, then you must set pressure
sensor as "Not used", otherwise oil pressure low alarm shutdown may appear.
— Can set several points of forehand or backmost as the same ordinate, as the following picture:
N/m
1Pa
1kgf/cm
2
9.8x10
1bar
1psi
6.89x10
HGM6100LT Series Genset Controller User Manual
Fig.4 – Sensor Curve
Table 12 – Conventional Pressure Unit Conversion Table
2
(pa)
1
1.02x10
4
5
1x10
3
7.03x10
kgf/cm
2
5
1
1.02
2
6.89x10
o
C resistor type); If it is set as SGD
bar
5
1x10
1.45x10
0.98
1
2
Page 35 of 50
psi
4
14.2
14.5