SENSOR SETTING

1) When reselect sensors, the sensor curve will be transferred into the standard value. For example,
if temperature sensor is SGH (120°C resistor type), its sensor curve is SGH (120°C resistor type);
if select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
2) When there is difference between standard sensor curves and using sensor, user can adjust it in
"curve type".
3) When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
4) If select sensor type as "None", sensor curve is not working and LCD does not display the sensor
information.
5) If there is no oil pressure sensor, but there is low oil pressure alarm switch, user must set the oil
pressure sensor as "None", otherwise, maybe low oil pressure shutdown occurs.
6) The headmost or backmost values in the vertical coordinates can be set as same as below:
1Pa
2
1kgf/cm
1bar
1psi
HGM410DC Genset Controller
Common unit conversion table
2
N/m
(pa)
kgf/cm
1
1.02x10
4
9.8x10
5
1x10
3
6.89x10
7.03x10
2015-11-12
HGM410DC Genset Controller User Manual
2
bar
5
1x10
1
0.98
1.02
2
6.89x10
Version 1.0
(p/in
5
1.45x10
14.2
1
14.5
2
Page 29 of 34
2
.psi)
4
1