8.2 DEFINABLE CONTENTS OF PROGRAMMABLE OUTUT PORTS

Table 14 Definable Contents of Programmable Output Ports
No.
0
Not Used
1-6
Reserved
7
Custom Combined 1
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13-17
Reserved
18
Audible Alarm
19-25
Reserved
26
Remote Control Output
27-28
Reserved
29
Bus Close Output
30
Bus Open Output
31
Mains Close Output
32
Mains Open Output
33-43
Reserved
44
Bus OK
45
Reserved
46
Mains normal output
47
Synchronizing
48
Common Alarm
49
Common Trip and Stop
50
Common Shutdown
51
Common Trip
52
Common Warning
HGM8156 Genset Parallel (With Mains) Controller
HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
Range
(0-500)%
(0-2000)%
(0-500)%
(0-2000)%
Type
For details of function description please see the following
contents.
Act at warning, shutdown, and trips; Can connect an
announciator externally; When "alarm mute" configurable input
port is active, it is prohibited to output;
This port is controlled by communication (PC).
Control bus to take load.
Control bus to unload.
Control mains to take load.
Control mains to unload;
Act when bus voltage is normal.
Act at genset common warning, common shutdown, common
trip alarms.
Act at common trip and stop alarms.
Act at common shutdown alarms.
Act at common trip alarms without stop.
Act at common warning alarms.
Defaults
20
Regulate and control before parallel;
20
Regulate and control before parallel;
20
Regulate and control after parallel;
20
Regulate and control after parallel;
Description
2019-09-10
Description
Version 1.1
Page 28 of 44