7.3 DEFINABLE CONTENTS OF PROGRAMMABLE INPUT PORTS 1-7

Table 12 - Definable Contents of Programmable Inputs 1~7(Ground connected (B-) is active.)
No.
Items
0
Not Used
1
Alarm Mute
2
Reset Alarm
3
Emergency Stop
4
High Temp Shutdown
5
Low OP Shutdown
6
Fuel Level Warn
7
Warn Input
8
Shutdown Input
9
Remote Start Onload
10
Remote Start Offload
11
Reset Maint. Time
12
Panel Lock
13
Inhibit Timing Start
14
Inhibit Auto Start
15
Remote Control
16
Charge Alt Fail IN
17
Low Oil Level Warn
18
Manual/Auto Switch
19
Reserved
20
Idle Input
21
Reserved
22
Control At Gate
23
Aux. Mains Fail
24
Aux. Mains OK
25
Pile Under Volt
26
Reserved
27
Reserved
28
Reserved
29
Reserved
30
Reserved
31
Reserved
HGM4020DC Genset Controller
HGM4020DC GENSET CONTROLLER USER MANUAL
Input port is inactive.
If input port is active, "audible alarm" output will be inhibited.
If input port is active, shutdown alarms and ELE trip alarms can be
reset.
If input port is active, genset will alarm shutdown immediately.
After safety on delay is expired, if this input is active, genset will alarm
shutdown immediately.
After safety on delay is expired, if this input is active, genset will alarm
shutdown immediately.
If this input is active, controller will send low fuel level warning alarm
signal.
If this input is active, controller will send external warning alarm
signal.
If this input is active, genset will alarm shutdown immediately.
When this input is active in auto mode, genset starts automatically
and takes on load after normal running. Otherwise, genset will stop
automatically if this input is deactivated.
When this input is active in auto mode, genset starts automatically
and without taking load after normal running. Otherwise, genset will
stop automatically if this input is deactivated.
When this input port is valid, reset the maintenance time countdown,
it is invalid for the maintenance date.
When input is active, all keys expect
display on the right side of fifth line of LCD main page.
When input port is active in auto mode, genset scheduled run is
inhibited.
When input port is active in auto mode, genset auto start is inhibited.
When the input is active, keys on the panel are locked except for
keys and remote mode will display on the LCD. Remote
module pattern and start/stop operation can be switched by keys on
the panel.
When the input is active, controller will send failed to charge warning.
When input port is active, controller will initiate low oil level warning
alarm.
When input is active, it switches to auto mode automatically, panel
buttons and local operation are inactive; When input is inactive, it
switches to manual mode automatically, remote operation is inhibited.
When the input is active, idle speed control starts outputting.
When the input is active, controller will send access control input
warning.
Simulate mains is abnormal.
Simulate mains is normal.
When the input is active, it is considered battery is under voltage. If
crank disconnect conditions are configured, genset will be started in
auto mode.
Version 1.0