Advertisement

Parameter Description
8-13 Configurable Status Word STW
Option:
[65] Comtor 5
3
3
[70] Logic Rule 0 See parameter group 13-4*. If Logic Rule 0 is
[71] Logic Rule 1 See parameter group 13-4*. If Logic Rule 1 is
[72] Logic Rule 2 See parameter group 13-4*. If Logic Rule 2 is
[73] Logic Rule 3 See parameter group 13-4*. If Logic Rule 3 is
[74] Logic Rule 4 See parameter group 13-4*. If Logic Rule 4 is
[75] Logic Rule 5 See parameter group 13-4*. If Logic Rule 5 is
[80] SL Digital
Output A
[81] SL Digital
Output B
[82] SL Digital
Output C
[83] SL Digital
Output D
[84] SL Digital
Output E
[85] SL Digital
Output F
80
®
VLT
Function:
See parameter group 13-1*. If Comtor 5 is
evaluated as TRUE, the output goes high.
Otherwise, it is low.
evaluated as TRUE, the output goes high.
Otherwise, it is low.
evaluated as TRUE, the output goes high.
Otherwise, it is low.
evaluated as TRUE, the output goes high.
Otherwise, it is low.
evaluated as TRUE, the output goes high.
Otherwise, it is low.
evaluated as TRUE, the output goes high.
Otherwise, it is low.
evaluated as TRUE, the output goes high.
Otherwise, it is low.
See 13-52 SL Controller Action. The output
goes high whenever the Smart Logic Action
[38] Set digital out A high is executed. The
output goes low whenever the Smart Logic
Action [32] Set digital out A low is executed.
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [39]
Set digital out B high is executed. The input
goes low whenever the Smart Logic Action
[33] Set digital out B low is executed.
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [40]
Set digital out C high is executed. The input
goes low whenever the Smart Logic Action
[34] Set digital out C low is executed.
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [41]
Set digital out D high is executed. The input
goes low whenever the Smart Logic Action
[35] Set digital out D low is executed.
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [42]
Set digital out E high is executed. The input
goes low whenever the Smart Logic Action
[36] Set digital out E low is executed.
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [43]
Set digital out F high is executed. The input
goes low whenever the Smart Logic Action
[37] Set digital out F low is executed.
MG16H102 - VLT
Refrigeration Drive Programming Guide
3.9.4 8-3* FC Port Settings
8-30 Protocol
Protocol selection for the integrated FC (standard) Port (RS-485)
on the control card.
Parameter group 8-7* is only visible when FC Option [9] is
chosen.
Option:
[0]
FC
*
[1]
FC MC
[2]
Modbus
RTU
[3]
Metasys N2
[9]
FC option
NOTE
Further details can be found in the BACnet and Metasys
manuals.
8-31 Address
Range:
Size related
*
®
is a registered Danfoss trademark
Function:
Communication according to the FC Protocol
as described in the VLT Refrigeration Drive FC
103 Design Guide, chapter: RS-485 Installation
and Set-up.
Same as FC [0] but to be used when
downloading SW to the frequency converter
or uploading dll file (covering information
regarding parameters available in the
frequency converter and their inter-depend-
encies) to Motion Control Tool MCT10.
Communication according to the Modbus
RTU protocol as described in the VLT Refrig-
eration Drive FC 103 Design Guide, chapter:
RS-485 Installation and Set-up.
Communication protocol. The N2 software
protocol is designed to be general in nature
in order to accommodate the unique
properties each device may have. Please see
sete manual VLT
®
HVAC Drive Metasys,
MG11Gxyy.
To be used when a gateway is connected to
the integrated RS-485 port, e.g. the BACnet
gateway.
Following changes will take place:
-Address for the FC port will be set to 1 and
8-31 Address is now used to set the address
for the gateway on the network, e.g. BACnet.
®
Please see sete manual VLT
BACnet, MG11DXYY.
-Baud rate for the FC port will be set to a
fixed value (115.200 Baud) and 8-32 Baud
Rate, is now used to set the baud rate for the
network port (e.g. BACnet) on the gateway.
Function:
[ 1 - 126 ] Enter the address for the FC (standard)
port.
Valid range: 1-126.