Parameter Description
8-32 Baud Rate
Option:
Function:
Baud rates 9600, 19200, 38400 and 76800
baud are valid for BACnet only.
[0]
2400 Baud
[1]
4800 Baud
[2]
9600 Baud
*
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
Function:
Parity and Stop Bits for the protocol
8-30 Protocol using the FC Port. For
some of the protocols, not all
options are visible. Default depends
on the protocol selected.
[0]
Even Parity, 1 Stop Bit
*
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Function:
Size related
[
5 - 10000
Specify the minimum delay time
*
ms]
between receiving a request and
transmitting a response. This is
used for overcoming modem
turnaround delays.
8-36 Maximum Response Delay
Range:
Function:
Size related
[ 11 - 10001
Specify the maximum permissible
*
ms]
delay time between transmitting a
request and receiving a response.
Exceeding this delay time will cause
control word time-out.
8-37 Maximum Inter-Char Delay
Range:
Function:
Size related
[ 0.00 - 35.00
Specify the maximum permissible
*
ms]
time interval between receipt of
two bytes. This parameter activates
time-out if transmission is
interrupted.
®
VLT
Refrigeration Drive Programming Guide
3.9.5 8-4* Telegram Selection
8-40 Telegram Selection
Option:
[1]
[101] PPO 1
[102] PPO 2
[103] PPO 3
[104] PPO 4
[105] PPO 5
[106] PPO 6
[107] PPO 7
[108] PPO 8
[200] Custom telegram 1
8-45 BTM Transaction Command
Option:
[0]
8-46 BTM Transaction Status
Option:
[0]
[1]
[2]
[3]
[4]
[5]
8-47 BTM Timeout
Range:
60 s
3.9.6 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus
merging.
NOTE
These parameters are active only when 8-01 Control Site is
set to [0] Digital and control word.
8-50 Coasting Select
Option:
[0]
[1]
®
MG16H102 - VLT
is a registered Danfoss trademark
Function:
Enables use of freely configurable
telegrams or standard telegrams for
the FC port.
Standard telegram 1
*
Off
Off
Transaction Started
Transaction Comitting
Transaction Timeout
Err. Non-existing Par.
Err. Par. Out of Range
[0 - 360 s]
*
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
Digital
Activates Start command via a digital input.
input
Bus
Activates Start command via the serial
communication port or fieldbus option.
Function:
Function:
Function:
81