Parameter Description
22-84 Speed at No-Flow [Hz]
Range:
Function:
Size
[ 0 - par.
Resolution 0.033 Hz.
related
22-86 Hz]
*
The speed of the motor at which flow has
effectively stopped and minimum
pressure H
entered here in Hz. Alternatively, the
speed in RPM can be entered in
22-83 Speed at No-Flow [RPM]. If it has
been decided to use Hz in 0-02 Motor
Speed Unit then 22-86 Speed at Design
Point [Hz] should also be used. Closing
the valves and reducing the speed until
minimum pressure H
determine this value.
22-85 Speed at Design Point [RPM]
Range:
Function:
Size
[
par.
Resolution 1 RPM.
related
22-83 -
*
Only visible when 22-82 Work Point
60000
Calculation is set to Disable. The speed
RPM]
of the motor at which the System
Design Working Point is achieved should
be entered here in RPM. Alternatively,
the speed in Hz can be entered in
22-86 Speed at Design Point [Hz]. If it has
been decided to use RPM in 0-02 Motor
Speed Unit then 22-83 Speed at No-Flow
[RPM] should also be used.
22-86 Speed at Design Point [Hz]
Range:
Function:
Size
[
par.
Resolution 0.033 Hz.
related
22-84 -
*
Only visible when 22-82 Work Point
par. 4-19
Calculation is set to Disable. The speed of
Hz]
the motor at which the System Design
Working Point is achieved should be
entered here in Hz. Alternatively, the
speed in RPM can be entered in
22-85 Speed at Design Point [RPM]. If it
has been decided to use Hz in
0-02 Motor Speed Unit, then 22-83 Speed
at No-Flow [RPM] should also be used.
22-87 Pressure at No-Flow Speed
Range:
Function:
0
[ 0 - par. 22-88 ] Enter the pressure H
*
Speed at No Flow in Reference/Feedback
Units.
Also see 22-82 Work Point Calculation point D.
®
VLT
Refrigeration Drive Programming Guide
is achieved should be
MIN
is achieved will
MIN
corresponding to
MIN
®
MG16H102 - VLT
is a registered Danfoss trademark
22-88 Pressure at Rated Speed
Range:
999999
[
par. 22-87 -
*
999999.999 ]
Also see 22-82 Work Point Calculation point A.
22-89 Flow at Design Point
Range:
Function:
0
[0 - 999999.999 ] Enter the value corresponding to the
*
Flow at Design Point. No units necessary.
Also see 22-82 Work Point Calculation point C.
22-90 Flow at Rated Speed
Range:
Function:
0
[0 - 999999.999 ] Enter the value corresponding to Flow at
*
Rated Speed. This value can be defined
using the pump datasheet.
Function:
Enter the value corresponding to
the Pressure at Rated Speed, in
Reference/Feedback Units. This
value can be defined using the
pump datasheet.
139