Parameter Description
26-15 Term. X42/1 High Ref./Feedb. Value
Range:
100
[-999999.999 -
*
999999.999 ]
3
3
26-16 Term. X42/1 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
26-17 Term. X42/1 Live Zero
Option:
[0]
Disabled
[1]
Enabled
*
3.20.3 26-2* Analog Input X42/3
26-20 Terminal X42/3 Low Voltage
Range:
0.07 V
[
*
6-31 V]
26-21 Terminal X42/3 High Voltage
Range:
10 V
[
par. 6-30 -
*
10 V]
26-24 Term. X42/3 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999 ]
160
VLT
Function:
Enter the analog input scaling
value that corresponds to the high
voltage value set in 26-11 Terminal
X42/1 High Voltage.
Function:
Enter the time constant. This is a first-
order digital low pass filter time constant
for suppressing noise in terminal X42/1. A
high time constant value improves
dampening but also increases the time
delay through the filter.
NOTE
This parameter cannot be adjusted
while the motor is running.
Function:
This parameter makes it possible to enable the
Live Zero monitoring. E.g. where the analog input
is a of the frequency converter control, rather
than being used as of a decentral I/O system,
such as a Building Management System.
Function:
0 - par.
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
26-24 Term. X42/3 Low Ref./Feedb. Value.
Function:
Enter the high voltage value. This analog
input scaling value should correspond to
the high reference/feedback value set in
26-25 Term. X42/3 High Ref./Feedb. Value.
Function:
Enter the analog input scaling value
that corresponds to the low voltage
value set in 26-20 Terminal X42/3 Low
Voltage.
MG16H102 - VLT
®
Refrigeration Drive Programming Guide
26-25 Term. X42/3 High Ref./Feedb. Value
Range:
100
[-999999.999 -
*
999999.999 ]
26-26 Term. X42/3 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
26-27 Term. X42/3 Live Zero
Option:
[0]
Disabled
[1]
Enabled
*
3.20.4 26-3* Analog Input X42/5
26-30 Terminal X42/5 Low Voltage
Range:
0.07 V
[
*
6-31 V]
26-31 Terminal X42/5 High Voltage
Range:
10 V
[
*
10 V]
26-34 Term. X42/5 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999 ]
®
is a registered Danfoss trademark
Function:
Enter the analog input scaling
value that corresponds to the high
voltage value set in 26-21 Terminal
X42/3 High Voltage.
Function:
Enter the time constant. This is a first-
order digital low pass filter time constant
for suppressing noise in terminal X42/3. A
high time constant value improves
dampening but also increases the time
delay through the filter.
NOTE
This parameter cannot be adjusted
while the motor is running.
Function:
This parameter makes it possible to enable the
Live Zero monitoring. E.g. where the analog input
is a of the frequency converter control, rather
than being used as of a decentral I/O system,
such as a Building Management System.
Function:
0 - par.
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
26-34 Term. X42/5 Low Ref./Feedb. Value.
Function:
par. 6-30 -
Enter the high voltage value. This analog
input scaling value should correspond to
the high reference/feedback value set in
26-35 Term. X42/5 High Ref./Feedb. Value.
Function:
Enter the analog input scaling value
that corresponds to the low voltage
value set in 26-30 Terminal X42/5 Low
Voltage.