Parameter Description
Events are logged with value, and time stamp in ms. The
time interval between two events depends on how often
events occur (maximum once every scan time). Data
logging is continuous but if an alarm occurs, the log is
saved and the values can be viewed on the display. This
feature is useful, for example when carrying out service
following a trip. View the historic log contained in this
parameter via the serial communication port or via the
display.
15-20 Historic Log: Event
Array [50]
Range:
Function:
0
[0 - 255 ]
View the event type of the logged events.
*
15-21 Historic Log: Value
Array [50]
Range:
Function:
0
[0 -
View the value of the logged event.
*
2147483647 ]
Interpret the event values according to
this table:
Digtal input
Digital output
(not
monitored in
this SW
release)
Warning word Decimal value. See
Alarm word
Status word
Control word
Extended
status word
Table 3.16
®
VLT
Refrigeration Drive Programming Guide
3.12.4 15-3* Alarm Log
Parameters in this group are array parameters, where up to
Decimal value. See
10 fault logs can be viewed. [0] is the most recent logged
16-60 Digital Input for
data, and [9] the oldest. Error codes, values, and time
description after
stamp can be viewed for all logged data.
converting to binary
value.
Decimal value. See
16-66 Digital Output [bin]
for description after
converting to binary
value.
16-92 Warning Word for
description.
Decimal value. See
16-90 Alarm Word for
description.
Decimal value. See
16-03 Status Word for
description after
converting to binary
value.
Decimal value. See
16-00 Control Word for
description.
Decimal value. See
16-94 Ext. Status Word for
description.
®
MG16H102 - VLT
is a registered Danfoss trademark
15-22 Historic Log: Time
Array [50]
Range:
Function:
0 ms
[0 - 2147483647
View the time at which the logged
*
ms]
event occurred. Time is measured in
ms since frequency converter start.
The max. value corresponds to
approx. 24 days which means that the
count will restart at zero after this
time period.
15-23 Historic log: Date and Time
Array [50]
Range:
Function:
Size related
[ 0 - 0 ] Array parameter; Date & Time 0 - 49: This
*
parameter shows at which time the
logged event occurred.
15-30 Alarm Log: Error Code
Array [10]
Range:
Function:
0
[0 - 255 ] View the error code and look up its meaning in .
*
15-31 Alarm Log: Value
Array [10]
Range:
Function:
0
[-32767 - 32767 ] View an extra description of the error.
*
This parameter is mostly used in
combination with alarm 38 'internal
fault'.
15-32 Alarm Log: Time
Array [10]
Range:
Function:
0 s
[0 - 2147483647 s] View the time when the logged event
*
occurred. Time is measured in seconds
from frequency converter start-up.
15-33 Alarm Log: Date and Time
Array [10]
Range:
Function:
Size related
[ 0 - 0 ] Array parameter; Date & Time 0 - 9: This
*
parameter shows at which time the
logged event occurred.
3
3
101