Parameter Description
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53. Current = 0;
Voltage = 1.
[0] Current
[1] Voltage
16-62 Analog Input 53
Range:
Function:
0
[-20 - 20 ]
View the actual value at input 53.
*
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54. Current = 0;
Voltage = 1.
[0] Current
[1] Voltage
16-64 Analog Input 54
Range:
Function:
0
[-20 - 20 ]
View the actual value at input 54.
*
16-65 Analog Output 42 [mA]
Range:
Function:
0
[0 - 30 ] View the actual value at output 42 in mA. The
*
value shown reflects the selection in 6-50 Terminal
42 Output.
16-66 Digital Output [bin]
Range:
Function:
0
[0 - 15 ]
View the binary value of all digital outputs.
*
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual frequency rate on terminal
*
29.
16-68 Pulse Input #33 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual value of the frequency
*
applied at terminal 33 as an impulse input.
16-69 Pulse Output #27 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of impulses applied to
*
terminal 27 in digital output mode.
16-70 Pulse Output #29 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of pulses to terminal 29
*
in digital output mode.
®
VLT
Refrigeration Drive Programming Guide
16-71 Relay Output [bin]
Range:
0
16-72 Counter A
Range:
0
16-73 Counter B
Range:
0
16-75 Analog In X30/11
Range:
0
16-76 Analog In X30/12
Range:
0
16-77 Analog Out X30/8 [mA]
Range:
0
3.13.5 16-8* Fieldbus & FC Port
Parameters for reporting the BUS references and control
words.
®
MG16H102 - VLT
is a registered Danfoss trademark
Function:
[0 - 31 ]
View the settings of all relays.
*
Illustration 3.40
Function:
[-2147483648 -
View the present value of Counter A.
*
2147483647 ]
Counters are useful as comtor operands,
see 13-10 Comparator Operand.
The value can be reset or changed either
via digital inputs (parameter group 5-1*)
or by using an SLC action (13-52 SL
Controller Action).
Function:
[-2147483648 -
View the present value of Counter B.
*
2147483647 ]
Counters are useful as comtor operands
(13-10 Comparator Operand).
The value can be reset or changed either
via digital inputs (parameter group 5-1*)
or by using an SLC action (13-52 SL
Controller Action).
Function:
[-20 - 20 ] View the actual value at input X30/11 of MCB
*
101.
Function:
[-20 - 20 ] View the actual value at input X30/12 of MCB
*
101.
Function:
[0 - 30 ]
View the actual value at input X30/8 in mA.
*
3
3
107