Danfoss VLT FC 103 Programming Manual page 88

Refrigeration drive
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Parameter Description
13-02 Stop Event
Option:
Function:
[83] Broken Belt
13-03 Reset SLC
Option:
Function:
[0]
Do not reset
Retains programmed settings in all
*
SLC
parameter group 13 parameters (13-**).
[1]
Reset SLC
Resets all parameter group 13 parameters
(13-**) to default settings.
3.10.3 13-1* Comtors
13-10 Comparator Operand
Array [5]
Option:
Function:
Select the variable to be monitored
by the comtor.
[0]
DISABLED
*
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor Current
[5]
Motor torque
[6]
Motor power
[7]
Motor voltage
[8]
DC-link voltage
[9]
Motor Thermal
[10] Drive thermal
[11] Heat sink temp.
[12] Analog input AI53
[13] Analog input AI54
[14] Analog input AIFB10
[15] Analog input AIS24V
[17] Analog input AICCT
[18] Pulse input FI29
[19] Pulse input FI33
[20] Alarm number
[30] Counter A
[31] Counter B
13-11 Comparator Operator
Array [6]
Option:
Function:
[0]
<
Select [0] < for the result of the evaluation to be
*
TRUE, when the variable selected in
13-10 Comparator Operand is smaller than the
fixed value in 13-12 Comparator Value. The result
will be FALSE, if the variable selected in
13-10 Comparator Operand is greater than the
fixed value in 13-12 Comparator Value.
®
VLT
Refrigeration Drive Programming Guide
13-11 Comparator Operator
Array [6]
Option:
[1]
[2]
13-12 Comparator Value
Array [6]
Range:
Size related
3.10.4 13-2* Timers
Use the result (TRUE or FALSE) from timers directly to
define an event (see 13-51 SL Controller Event), or as
boolean input in a logic rule (see 13-40 Logic Rule Boolean
1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule Boolean 3).
A timer is only FALSE when started by an action (i.e. [29]
Start timer 1) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Array [8]
Range:
Size related
3.10.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE/FALSE inputs)
from timers, comtors, digital inputs, status bits and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in 13-40 Logic Rule
Boolean 1, 13-42 Logic Rule Boolean 2 and 13-44 Logic Rule
Boolean 3. Define the operators used to logically combine
the selected inputs in 13-41 Logic Rule Operator 1 and
13-43 Logic Rule Operator 2.
®
MG16H102 - VLT
is a registered Danfoss trademark
Function:
≈ (equal) Select [1] ≈ for the result of the evaluation to be
TRUE, when the variable selected in
13-10 Comparator Operand is approximately equal
to the fixed value in 13-12 Comparator Value.
>
Select [2] > for the inverse logic of option [0] <.
Function:
[-100000 -
Enter the 'trigger level' for the
*
100000 ]
variable that is monitored by this
comtor. This is an array parameter
containing comtor values 0 to 5.
Function:
[ 0 - 0 ] Enter the value to define the duration of
*
the FALSE output from the programmed
timer. A timer is only FALSE if it is started
by an action (i.e. [29]vStart timer 1) and
until the given timer value has elapsed.
3
3
87