Danfoss VLT FC 103 Programming Manual page 97

Refrigeration drive
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Parameter Description
14-40 VT Level
Range:
66 %
[40 - 90 %] Enter the level of motor magnetisation at
*
3
3
NOTE
This parameter cannot be adjusted while the motor is
running.
NOTE
This parameter is not active when 1-10 Motor Construction
is set to [1] PM non salient SPM.
14-41 AEO Minimum Magnetisation
Range:
Size related
*
%]
NOTE
This parameter is not active when 1-10 Motor Construction
is set to [1] PM non salient SPM.
14-42 Minimum AEO Frequency
Range:
10 Hz
[5 - 40 Hz] Enter the minimum frequency at which the
*
NOTE
This parameter is not active when 1-10 Motor Construction
is set to [1] PM non salient SPM.
14-43 Motor Cosphi
Range:
Size
related
0.95 ]
*
NOTE
This parameter is not active when 1-10 Motor Construction
is set to [1] PM non salient SPM.
3.11.6 14-5* Environment
These parameters help the frequency converter to operate
under special environmental conditions.
96
Function:
low speed. Selection of a low value reduces
energy loss in the motor, but also reduces
load capability.
Function:
[40 - 75
Enter the minimum allowable magnet-
isation for AEO. Selection of a low
value reduces energy loss in the
motor, but can also reduce resistance
to sudden load changes.
Function:
Automatic Energy Optimisation (AEO) is to
be active.
Function:
[0.40 -
The Cos(phi) setpoint is automatically
set for optimum AEO performance
during AMA. This parameter should
normally not be altered. However in
some situations it may be necessary to
enter a new value to fine-tune.
MG16H102 - VLT
®
VLT
Refrigeration Drive Programming Guide
14-50 RFI Filter
This parameter is only available for . It is not relevant to due to
different design and shorter motor cables.
Option:
[0]
Off Select [0] Off if the frequency converter is fed by an
[1]
On Select [1] On to ensure that the frequency converter
*
Illustration 3.34
14-52 Fan Control
Option:
[0]
Auto
*
[1]
On 50%
[2]
On 75%
[3]
On 100%
14-53 Fan Monitor
Option:
[0]
Disabled
[1]
Warning
*
[2]
Trip
14-55 Output Filter
Option:
®
is a registered Danfoss trademark
Function:
isolated mains source (IT mains).
If a filter is used, select Off [0] during charging to
prevent a high leakage current making the RCD
switch.
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
complies with EMC standards.
Function:
Select the minimum speed of the main fan.
Select [0] Auto to run the fan only when the
internal temperature of the frequency converter
is in the range +35 °C to approximately +55 °C.
The fan will run at low speed at +35 °C and at
full speed at approximately +55 °C.
Function:
Select which reaction the frequency converter
should take in case a fan fault is detected.
Function:
Select the type of output filter connected. This
parameter cannot be adjusted while motor is
running.