Grounding Instructions; Ac Power; Supplying Power To The Unit; Ac Powered Systems - ADTRAN Total Access 600R System Manual

Hide thumbs Also See for Total Access 600R:
Table of Contents

Advertisement

Section 3 Network Turnup Procedure
2 Mounting Brackets (P/N 3265421@C)
4 Screws (P/N 3276003003)
RJ-45 to DB-9 Adapter (P/N 3196ADPT001)
The Total Access 600R base unit.
Customers must supply the Ethernet cable.
4.

GROUNDING INSTRUCTIONS

The following provides grounding instruction information from the Underwriters' Laboratory UL 60950
Standard for Safety of Information Technology Equipment Including Electrical Business Equipment, with
revisions dated March 15, 2002.

AC Power

The attachment-plug receptacles in the vicinity of the product or system are all to be of a grounding type,
and the equipment grounding conductors serving these receptacles are to be connected to earth ground at
the service equipment.
5.

SUPPLYING POWER TO THE UNIT

AC Powered Systems

The AC powered unit comes equipped with a detachable power cord with a 3-prong plug for connecting to
a grounded power receptacle. As shipped, the unit is set to factory default conditions. After installing the
chassis, the unit is ready for power-up. To power-up the unit, ensure that the unit is properly connected to
an appropriate power source.
This unit shall be installed in accordance with Article 400 and 364.8 of the NEC NFPA
70 when installed outside of a Restricted Access Location (i.e., central office, behind a
locked door, service personnel only area).
Power to the unit's AC system must be from a grounded 90-125 VAC, 60 Hz source.
The power receptacle uses double-pole, neutral fusing.
Maximum recommended ambient operating temperature is 45 ºC.
32
© 2002 ADTRAN, Inc
Total Access 600R System Manual
61200600L1-1A