Wiring of external device and I/O terminal block

Wiring of screw terminal block
■Tightening torque
Tighten the terminal screw within the following specified torque range.
Tightening the screw too much may damage the module case.
Screw type
Terminal screw (M3  5.2 screw)
■Wire to be used
The following table describes the wire to be connected to the screw terminal block.
Diameter
22 to 14 AWG
■Applicable solderless terminal
The following table lists the applicable solderless terminal.
Model name
RAV1.25-3
V2-MS3
RAP2-3SL
TGV2-3N
■Signal name and wiring
For the signal names of the terminal block and wiring of the external device, refer to the specifications of each module.
Incorrect wiring can cause malfunction of or damage on the module.
Page 16 Performance Specifications
■Wiring method
(1)
• Do not put oil on the terminal and screw. Failure to do so may damage the screw.
• The number of the applicable solderless terminals must be two or less. When inserting two applicable
solderless terminals, insert them back-to-back. Otherwise the screw cannot be tightened and it may
damage the screw.
• Tighten the terminal screw with an applicable driver. Tightening with an inapplicable driver may damage the
screw.
6 INSTALLATION AND WIRING
62
6.5 Wiring
Type
Stranded
Applicable wire size
0.3 to 1.25
1.25 to 2.0
1.25 to 2.0
1.25 to 2.0
Tightening torque range
0.59 to 0.88Nm
Material
Copper
Contact
JST Mfg. Co., Ltd.
Nippon Tanshi Co., Ltd.
NICHIFU Co., Ltd.
1.
Loosen the terminal screw. Connect the round
solderless terminal (1) as it is.
Temperature rating
75 or more