00809-0100-4530
Table I-2: Alarm Levels of Priority
Priority number
0
1
2
3-7
8-15
I.5

Process alarms

Process Alarm detection is based on the OUT value. Configure the alarm limits of the
following standard alarms:
High (HI_LIM)
High high (HI_HI_LIM)
Low (LO_LIM)
Low low (LO_LO_LIM)
To avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm
hysteresis in percent of the PV span can be set using the ALARM_HYS parameter.
The priority of each alarm is set in the following parameters:
HI_PRI
HI_HI_PRI
LO_PRI
LO_LO_PRI
I.6

Recommended actions for alerts

I.6.1
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will give a
recommended course of action to take based on which type and which specific event of
the alerts are active.
Table I-3: RB.RECOMMENDED_ACTION
Alerts
Reference Manual
Priority description
The alarm condition is not used.
An alarm condition with a priority of 1 is recognized by the system, but is
not reported to the operator.
An alarm condition with a priority of 2 is reported to the operator.
Alarm conditions of priority 3 to 7 are advisory alarms of increasing
priority.
Alarm conditions of priority 8 to 15 are critical alarms of increasing
priority.
Alarm type
None
Failed/Maint/Advise Active
event
None
Resource Transducer Block
April 2019
Recommended action text
string
No action required