Table J-3: Alarm Level Priority
Priority Number
0
1
2
3-7
8-15
J.7.1
Status handling
Normally, the status of the PV reflects the status of the measurement value, the operating
condition of the I/O card, and any active alarm condition. In Auto mode, OUT reflects the
value and status quality of the PV. In Man mode, the OUT status constant limit is set to
indicate that the value is a constant and the OUT status is Good.
The Uncertain - EU range violation status is always set, and the PV status is set high- or low-
limited if the sensor limits for conversion are exceeded.
In the STATUS_OPTS parameter, you can select from the following options to control the
status handling:
BAD if Limited
Uncertain if Limited
Uncertain if in
Manual mode
Note
The instrument must be in Manual or Out of Service mode to set the status option. The AI
block only supports the BAD if Limited option. Unsupported options are not grayed out;
they appear on the screen in the same manner as supported options.
J.8

Advanced features

The AI function block provided with Fisher
capability through the addition of the following parameters:
ALARM_TYPE Allows one or more of the process alarm conditions detected by the AI
Reference Manual
Priority Description
The priority of an alarm condition changes to 0 after the
condition that caused the alarm is corrected.
An alarm condition with a priority of 1 is recognized by
the system, but is not reported to the operator.
An alarm condition with a priority of 2 is reported to the
operator, but does not require operator attention (such
as diagnostics and system alerts).
Alarm conditions of priority 3 to 7 are advisory alarms of
increasing priority.
Alarm conditions of priority 8 to 15 are critical alarms of
increasing priority.
Sets the OUT status quality to Bad when the value is higher or
lower than the sensor limits.
Sets the OUT status quality to Uncertain when the value is
higher or lower than the sensor limits.
The status of the Output is set to Uncertain when the mode is
set to Manual.
function block to be used in setting its OUT_D parameter.
-Rosemount
fieldbus devices provides added
Analog-Input Block
April 2019