Switch Alarm Limits (Hart ® Only) - Emerson 5301HxxxxxxxxxxxxxxZZ Series Reference Manual

Guided wave radar level transmitter
Table of Contents

Advertisement

Reference Manual
00809-0100-4530
Figure D-15: Configure Transmitter Variables for Signal Quality Metrics
D.8
Switch alarm limits (HART
D.8.1
Switch alarm limits using AMS Device Manager
The alarm limits can be set to either Rosemount or NAMUR NE43 values.
Prerequisites
Requires firmware version 2.L3 or later.
Procedure
1. Select Configure → Manual Setup → Device Setup.
2. Select the Analog Output tab.
3. Click the Configure Alarm and Saturation Limits button.
4. Select the desired alarm limit option, and then select Next.
5. Select Finish when the Method Complete message appears.
D.8.2
Switch alarm limits using handheld communicator
The alarm limits can be set to either Rosemount or NAMUR NE43 values.
Prerequisites
Requires firmware version 2.L3 or later.
Reference Manual
The Alarm Output Level drop-down list displays the current alarm limit option.
Advanced configuration
®
only)
April 2019
417