Configuring Alarms And Assigning Setpoints - Emerson Rosemount FCL-01 Reference Manual

Hide thumbs Also See for Rosemount FCL-01:
Table of Contents

Advertisement

Reference Manual
00809-0100-3412
4.4 

Configuring alarms and assigning setpoints

4.4.1 
Purpose of configuring alarms and setpoints
This section describes how to configure and assign setpoints to the alarm relays, simulate
alarm action, and synchronize interval timers.
Note
Configure the alarms first.
1. Configuring an alarm means:
2. Simulating an alarm means making the transmitter energize or de-energize an
4.4.2 
Definitions of alarms and setpoints
Assigning
alarms
Fault alarm
Alarm logic,
setpoints, and
deadbands
Rosemount FCL 1056
a. Assigning a sensor and measurement (chlorine, pH, or temperature) to an
alarm. An alarm relay can also be used as a timer.
b. Selecting high or low logic.
c. Choosing the deadband.
d. Setting the interval timer parameters.
alarm relay.
There are four alarm relays. The relays are freely assignable to any
sensor and to either the measurement (for example, chlorine) or
temperature. Alarm relays can also be assigned to operate as interval
timers or as fault alarms. A fault alarm activates when the transmitter
detects a fault in either itself of the sensor.
A fault condition exists when the transmitter detects a problem with
the sensor or with the transmitter itself that is likely to cause seriously
erroneous readings. If an alarm was programmed as a fault alarm, the
alarm activates. At the same time, a fault message appears in the main
display.
See
Figure 4-1
and
Figure
4-2.
Programming the transmitter
October 2023
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount fcl-02

Table of Contents