Emerson 5301HxxxxxxxxxxxxxxZZ Series Reference Manual page 186

Guided wave radar level transmitter
Table of Contents

Advertisement

Service and troubleshooting
April 2019
Table 7-17: Troubleshooting Chart
Symptom
F
Fieldbus Card to
OUNDATION
Transmitter Communication
Fault
Level Measurement Failure
Temperature Measurement
Failure
Volume Measurement Failure
No surface echo
DB Error/ Microwave Unit
Error/ Configuration Error/
Other Error
SW Error/ Display Error/
Analog Out Error
(1)
A malfunctioning display panel may only be replaced by service personnel at the Emerson service department. A display
must not be replaced when the transmitter is in operation.
(2)
If the Rosemount 5300 Level Transmitter has been exposed to temperatures outside the specified limits, the device may
stop its normal operation.
186
(continued)
Possible cause
Reference Manual
00809-0100-4530
Action
Verify Device Mode setting, should be
F
Fieldbus (Parameter:
OUNDATION
ENV_DEVICE_MODE)
Restart method from Resource Block
Reboot gauge (Cycle Power)
Check Power Supply
Check the gauge configuration
(Transducer Block)
Check that the mechanical installation
is correct
Check ambient temperature
Restart gauge
Contact Emerson Service Department
Restart gauge
Check gauge configuration using PC
Based configuration tool
Check signal strength
Restart transmitter
See
Example 1: Product surface peak
not found
Restart transmitter
Set database to default; load default
Database
Download Application Software
Call Service Center
Restart transmitter
Call Service Center
Rosemount 5300 Level Transmitter
(2)