Emerson 5301HxxxxxxxxxxxxxxZZ Series Reference Manual page 175

Guided wave radar level transmitter
Table of Contents

Advertisement

Reference Manual
00809-0100-4530
Table 7-4: Measurement Status
Message
Sim mode 0 active
Advanced Simulation Mode
active
Invalid Lower Volume Value
Invalid Upper Volume Value
Using probe end projection
measurement
Reference echo present
Sudden level jump detected
Nearzone echo present
Nonlinear gain used
Nearzone measurement
7.2.5
Interface status
Interface status messages that may appear on the Integral Display, on the handheld
communicator, in DeltaV, or in Rosemount Radar Master are shown in
Table 7-5: Interface Status
Message
Interface not OK
Interface not found
Can't measure interface on
horizontal probe
Reference Manual
(continued)
Description
The simulation mode is active. The given
measurements are simulated.
The advanced simulation mode is active.
The given lower volume value is invalid.
The given upper volume value is invalid.
The probe end projection is active in the
transmitter software.
An echo has been detected in the
reference zone.
This may result from various
measurement problems, such as:
Rapid level changes
Surface level within Blind Zone
Disturbing echo
An echo has been detected in the
nearzone.
The nonlinear gain is enabled.
The current sweep can be used as a
measurement of the nearzone.
Description
The interface measurement is not OK.
No interface available
Interface threshold to high
Interface cannot be measured when the
probe is horizontally mounted.
Service and troubleshooting
Action
Turn off the simulation mode.
To turn off the Advanced Simulation
mode, set Holding Register 3600=0 (see
View/edit holding
registers).
Check Lower Volume Status for details.
Check Upper Volume Status for details.
No action needed.
No action needed.
Check the tank to find out what causes
problem to track the surface.
Set the Rapid Level Changes
parameter, see
Rapid level
In the Blind Zones, the level may jump
to Full Tank/End of Probe
See
Disturbance echo
handling.
No action needed.
No action needed.
No action needed.
Table
7-5:
Action
Check other interface status messages
for reason.
No action needed.
Adjust Interface threshold, see
2: Interface peak not
found.
Change the probe mounting or turn off
interface measurement by changing the
measurement mode.
April 2019
changes.
Example
175