Rosemount 5300 with HART
April 2019
K.5.6
ScadaPack
Figure K-7: Wiring Diagram for Connecting Rosemount 5300 Modbus to SCADAPack
32
A. Rosemount 5300 Modbus
B. Power supply
C. + 8 to + 30 Vdc (max. rating)
D. SCADAPack32
Table K-11: Parameter Values (In Case of SCADAPack 32)
Parameter
Baud Rate
Floating Point Format Code
RTU Data Type
Input Register Base Number
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 5300 Level Transmitter. In this case, register 1302 needs to have 31303
entered as the address etc.
K.5.7
Kimray Inc. DACC 2000/3000
Table K-12
communication port must be configured to use "Tank Levels" protocol.
Table K-12: Kimray Inc. Input Types and Corresponding Values
Kimray Inc. Input Type
Tank Level1
Tank Level2
486
®
®
to Modbus
Converter
MA
MB
POWER +
POWER -
REF
shows input types in Kimray Inc. IMI software and the corresponding value. The
Rosemount 5300 Variable
PV
SV
RS-485 on COM1
1 +5 V
2 RX-
3 TX-
4 GND
5 RX+
6 TX+
7 Not Used
8 Not Used
Value
9600
0
Floating Point
30001
Reference Manual
00809-0100-4530
Format
ddd.dd.alt. -dd.dd
ddd.dd.alt -dd.dd
Rosemount 5300 Level Transmitter