Detailed Setup; 1Configure Process Alarms - Emerson Rosemount 2051 Wireless Series Reference Manual

Pressure, level, and flow solutions with wirelesshart protocol
Hide thumbs Also See for Rosemount 2051 Wireless Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4102, Rev AA
2.10

Detailed Setup

2.10.1
Configure Process Alarms
Alerts allow the user to configure the transmitter to output a HART message when the
configured data point is exceeded. A process alert will be transmitted continuously if the set
points are exceeded and the alert mode is ON. An alert will be displayed on a Field
Communicator, AMS status screen or in the error section of the LCD display. The alert will reset
once the value returns within range.
Note
HI alert value must be higher than the LO alert value. Both alert values must be within the
pressure or temperature sensor limits.
Example 1: Rising Alert
Example 2: Falling Alert
To configure the process alerts, perform the following procedure:
1.
2.
3.
Configuration
Fast Keys
2, 1, 5
Alert "OFF"
Alert "ON"
Deadband
Time
Alert "OFF"
Alert "ON"
Deadband
Time
From the Home screen, select 2: Configure.
Select 1: Guided Setup.
Select 5: Configure Process Alarms and follow the on-screen instructions to complete
configure of process alarms.
Alert "OFF"
Alert Set Point
Assigned Value
Assigned Value
Alert "OFF"
Alert Set Point
Section 2: Configuration
June 2012
19