Emerson 5301HxxxxxxxxxxxxxxZZ Series Reference Manual page 187

Guided wave radar level transmitter
Table of Contents

Advertisement

Reference Manual
00809-0100-4530
7.6.1
Troubleshooting the HART
Table 7-18: Troubleshooting the HART to Modbus converter
Symptom
No communication on RS-485 bus (MA, MB)
No Rosemount 5300 communication in
Rosemount Radar Master
No communication with Modbus RTU
protocol
No communication with Modbus ASCII
protocol
Reference Manual
®
to Modbus
Recommended actions
Check that the cables are connected.
Check that PWR+ is connected to + and PWR- is connected to - on the
power supply.
Make sure the Rosemount 5300 Level Transmitter is supplied with
8-30 Vdc (max. rating).
Try alternating MA/MB if you are unsure of the polarity.
If an RS-485 converter is used, make sure it is properly installed and
configured.
The last Rosemount 5300 Level Transmitter may need a terminating
120-Ω resistor connected between MA and MB.
Using HART+, HART-:
HART modem is not properly connected.
Polling address is incorrect in Rosemount Radar Master (default 1).
Using MA, MB:
See "No communication on RS-485 bus".
Polling address is incorrect in Rosemount Radar Master (default 1).
Cycle the power and wait 20 seconds before polling.
See "No communication on RS-485 bus".
Make sure the "Modbus communication protocol configuration" is
done properly, see
Modbus communication protocol
Make sure the Modbus RTU address is unique on the bus.
Cycle the power and try to connect.
Check the RTU communication settings.
See "No communication on RS-485 bus".
Make sure the "Modbus communication protocol configuration" is
done properly, see
Modbus communication protocol
Make sure the Modbus ASCII address is unique on the bus.
Cycle the power, waiting 40 seconds before communication begins.
Check the RTU communication settings.
Service and troubleshooting
April 2019
®
Converter
configuration.
configuration.
187