Configuration
July 2016
View Rosemount X-well measurement details
To view live data and trending for measured ambient temperature, measured surface
temperature, and calculated process temperature, perform the following procedure:
1.
2.
3.
4.
Figure 2-15. Rosemount X-well Measurement Details Page
2.9.3

Process alerts

Fast Key sequence
Process alerts allow the user to configure the transmitter to output a HART message when
the configured data point is exceeded. An alert will be transmitter continuously if the set
points are exceeded and the alert mode is ON. An alert will be displayed on a Field
Communicator, AMS Device Manager status screen or in the error section of the LCD
display. The alert will reset once the value returns within range.
Note
HI alert value must be higher than the LO alert value. Both alert values must be within the
temperature sensor limits.
24
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Right click on the device and select Configure.
In the menu tree, select Manual Setup.
Select the Sensor tab.
Select the Measurement Details button.
2, 1, 7
Reference Manual
00809-0200-4648, Rev BB
Configuration