Emerson 5301HxxxxxxxxxxxxxxZZ Series Reference Manual page 484

Guided wave radar level transmitter
Table of Contents

Advertisement

Rosemount 5300 with HART
April 2019
K.5.4
Thermo Electron Autopilot
Figure K-5: Wiring Diagram for Connecting Rosemount 5300 Modbus to Thermo
Electron Autopilot
A. Rosemount 5300 Modbus
B. Power supply
C. + 8 to + 30 Vdc (max. rating)
D. AutoPILOT
Table K-9: Parameter Values (In Case of Thermo Electron Autopilot)
Parameter
Baud Rate
Floating Point Format Code
RTU Data Type
Input Register Base Number
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 5300 Level Transmitter. In this case, register 1302 needs to have 1302 entered
as the address etc.
484
®
®
to Modbus
Converter
MA
MB
POWER +
POWER -
GND
CEB TB1
1 RX +
2 RX -
Value
9600
1
IEEE Flt 2R
0
Rosemount 5300 Level Transmitter
Reference Manual
00809-0100-4530