Outputs - Siemens SINUMERIK Series Function Manual

Safety integrated
Hide thumbs Also See for SINUMERIK Series:
Table of Contents

Advertisement

Commissioning - TM54F
4.5 Configuring the TM54F
● NC/NO contact (p10040)
Terminal property F-DI 0-9 (p10040.0 = F-DI 0, ... p10040.9 = F-DI 9). Only the property of
the second (lower) digital input is set. An NC contact is always connected to digital input 1
(upper). Digital input 2 can be configured as NO contact.
● Testing the F-DIs (p10041)
Using a checkmark at an F-DI, you can set as to whether for the particular F-DI a forced
checking procedure of the sensor power supply should be carried out.
● Status symbols
The status symbol after the AND logic element indicates the following state:
– red = discrepancy error at this F-DI
– yellow = discrepancy error at another F-DI
– gray = inactive
– blue = active
Parameter list
When required, alternatively you can use a parameter list for each setting in this window. You
can access the parameter list (Page 110) using the ">>" softkey followed by the "Parameter
list" softkey.
4.5.4

Outputs

The output terminals of the actual TM54F are shown in the the "Outputs" window. This involves
the following terminals:
● X523
● X525
● X533
● X535
These terminals are on the front side of the module. The terminals are displayed one above
the other in the window.
You can reach the lower terminals by scrolling (page up/page down). Alternatively, using the
"Select terminal" softkey, you can open a selection and select the terminal that is to be
displayed in the window.
You can make the following settings in the "Outputs" window:
106
Function Manual, 10/2015, 6FC5397-3EP40-5BA3
Safety Integrated