Adapting the terminal strip

5.3 Digital outputs

5.3
Digital outputs
Digital output terminals
BO: ryyxx.n
Table 5- 3
0
r0052.0
r0052.1
r0052.2
r0052.3
r0052.4
r0052.5
r0052.6
r0052.7
r0052.8
A complete list of the binector outputs is provided in the List Manual.
Table 5- 4
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, see the parameter list and the function block diagrams 2230 ff of the
List Manual.
88
p0730
p0731
p0732
Binector outputs of the inverter (selection)
Deactivating digital output
Drive ready
Drive ready for operation
Drive running
Drive fault active
OFF2 active
OFF3 active
Closing lockout active
Drive alarm active
Setpoint/actual value discrepancy
Example:
p0731
r0052.3
52.3
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Changing the function of the digital output
Interconnect the digital output with a binector output of your
choice.
Binector outputs are designated with "BO" in the parameter
list of the List Manual.
r0052.9
Process data control
r0052.10
f_actual >= p1082 (f_max)
r0052.11
Alarm: Motor current/torque limit
r0052.12
Brake active
r0052.13
Motor overload
r0052.14
Motor CW rotation
r0052.15
Inverter overload
r0053.0
DC braking active
r0053.2
f_actual > p1080 (f_min)
r0053.6
f_actual ≥ setpoint (f_setpoint)
Signal fault via digital output 1.
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD