Q61P/Q63P/Q64Pn - Mitsubishi Electric C80 Series Connection And Set Up Manual

Hide thumbs Also See for C80 Series:
Table of Contents

Advertisement

C80 Series Connection and Setup Manual
6 Wiring and Connecting

6.2.2 Q61P/Q63P/Q64PN

AC
Connect to 24VDC terminals
of I/O module that requires
24VDC internally.
*1: The ERR terminal turns ON/OFF as described below.
<When the power supply module is mounted on the main base unit>
The terminal turns OFF (opens) when the AC power is not input, a CPU module stop error (including a reset)
occurs, or the fuse of the power supply module is blown.
<When the power supply module is mounted on the extension base unit>
The terminal is always OFF (open).
*2: Be sure to ground the LG terminal of Q64PN, which are used as protective earth (PE).
(Note 1) Use the possibly thickest (up to 2 mm
terminals for the terminal block wiring. To prevent a short circuit caused by any loosen screws, use 0.8mm
thick crimp terminals with insulation sleeves. Up to 2 terminals can be attached to a terminal area.
(Note 2) Be sure to ground the earth terminal LG(PE) and FG (Ground resistance: 100Ω or less). If LG (PE) terminals
and FG terminals are connected without grounding the wires, the modules may be susceptible to noise. In
addition, since the LG terminals have potential of 1/2 input voltage, the operator may receive an electric shock
when touching metal parts.
(Note 3) No system error can be detected by the ERR terminal of an extension base unit. (ERR terminal is always set
off.)
100/200VAC
Fuse
AC
24VDC
DC
Ground
wire
Grounding
Extension
cable
100VAC
Ground
wire
Grounding
2
) wires for the 100/200 VAC and 24 VDC power cables. Always use crimp
CPU base unit (Q38B)
Q61P/Q63P/Q64PN
Extension base unit (Q68B)
Q61P/Q63P/Q64PN
77
QxxUD(H)CPU
ERR *1
LG(PE) *2
INPUT
100-240VAC
I/O module
ERR *1
LG(PE) *2
INPUT
100-240VAC
IB-1501452-C