simultaneously, then press 0, 1, 2 or 3 for the mode respectively. Type the
address (1-255) and press "Write". Wait for OK, address, mode info and a beep
(Press "Read" again to confirm). More info. on the backside of the tool.
3390
Label holder. To be mounted on the Analogue base (3312 / 4313 / 3379)
Intended for a label with "zone-address", "technical address", etc. to be read also
when the detector is plugged in its base. 100 label holders per packet. Excel
labels.
3391
Labels for 3390. A packet with self-adhesive white labels for label holder 3390. 10
A4-sheets, 132 labels for laser printer usage. The print-out is done via EBLWin.
9.1.2

Addressable I/O units

3361
Addressable multipurpose I/O unit.
The unit has two programmable inputs:
Monitored input
....used as zone line input (Z) (terminals 6 & 7): End-of-line capacitor 10uF
mounted in the last unit on the zone line. A short circuit on the input can generate
a fault or a fire alarm (set via EBLWin). This input is intended for conventional
detectors.
....used as general input (In0) (terminals 5 & 7): An input for NC or NO contacts
(set via EBLWin).
Isolated input (In1)
mA is required). Normally low or high (set via EBLWin).
The unit has two programmable relay
Relay output (Re0): NC or NO contacts (set via EBLWin).
Relay output (Re1): NC or NO contacts (set via EBLWin).
Connections and examples, see drawings F733 & F735. Unit dimensions: (L x W
x H) 90 x 70 x 32 mm. A plastic protection cover is attached. The cover dimensions:
(L x W x H) 129 x 73 x 45 mm.
3361 is intended to be surface mounted and for indoor use in dry premises. When
required, the unit can be mounted in a Waterproof (IP66 / 67) box. 3361 has an
LED to indicate communication to the unit or alarm condition.
information, see the Product Leaflet. The COM loop address is set with the
Address setting tool 3314 / 4414. The unit has an address label on which the unit's
COM loop address can be written.
The Address setting tool is also used for mode setting:
NORMAL mode: Used for 3361 in system FT1020G3.
3364 Addressable 2 voltage outputs unit. The unit is connected to a COM loop. External
24V
58
Also in an enclosed analogue heat detector (3309).
59
The same physical unit (3361) is also used in AS1668 Fan control applications and has a separate dialog box in EBLWin
60
470nF is revised to 10uF.
61
It is via EBLWin possible to define this input function to be a manual call point ("Used as MCP"), i.e. it cannot be disabled via
a time channel, cannot included in two-unit dependence or cannot use the "AVF" function.
62
Relay contacts: max. 2 A @ 30 V
61
Max. 1.5 mA, cable characteristic is max. 50 and max. 50nf.
(terminals 8 & 9): An optocoupler input (external 24 V
supply is required (via a 3366AU unit or FT1020G3).
DC
/ 125 V
.
DC
AC
Technical/Programming Manual
59
COM loop powered unit.
62
outputs:
61
FT1020G3 Rev 2.2.1
58
.
60
/ 8
DC