Input programming

Input programming is performed in EBLWin. Each input must have an individual Trigger
condition "Type" and Logic. It is not allowed to let two or more inputs have the same trigger
condition for some inputs.
11.1

Trigger conditions

The following trigger conditions are available (numbering only for the comments below):
0. Activated output (specified COM loop unit output)
1. Activated fault routing equipment (one input per C.U.)
2. Activated Fire Ventilation (one input per C.U.)
3. Activated key cabinet (one input per C.U.)
4. Activated Routing Equipment (one input per C.U.)
5. Alarm Key Cabinet (one input per Control Unit)
6. Alert Annunciation Acknowledge
7. Alert Annunciation Reset
8. Door Closing Test Input
9. Evacuate (one input per C.U.)
10. External Fault (max. 50 inputs per system)
11. External Time Channel (one input per time channel. 49 external time channels
e.g. 1049 are available per system)
12. Extinguishing alarm
13. Extinguishing start
14. Extinguishing stop
15. Extinguishing system fault (one input per C.U.)
16. Extinguishing system released (one input per C.U.)
17. Fault Signal External Fuses (one input per Control Unit)
18. Fault Signal External Power Supply (one input per Control Unit)
19. Fault warning routing equipment fault (one input per C.U.)
20. General Fire (max. 127 per C.U.)
21. Interlocking (400 inputs per C.U. / 4000 per system)
22. Loss of battery charger to external power supply (one input per C.U.)
23. Loss of main power source to external power supply (one input per C.U.)
24. Not used
25. NZ Silence switch
26. Pre-warning (input and corresponding fire alarm input have to be "connected" to
the same C.U.)
27. Technical warning (max. 100 per C.U.)
77
All inputs and outputs involved have to be connected to the same C.I.E.
78
Only valid for the New Zealand convention.
77
77
78
(one input per system)
75
Technical/Programming Manual
FT1020G3 Rev 2.2.1