4
Control & Indicating Equipment
4.1

FT1020G3 Specifications

The specifications of FT1020G3 Control Panel are shown in Table 1 below and the system
limitations are shown in Table 2 next page.

Table 1 Control Panel Specifications

Item
Mains Voltage
System Voltage
Current Consumption
Ambient Temperature (⁰C)
Ambient humidity (%RH)
Size (mm)
Enclosure Material
Enclosure Colour
Approvals
Standard Inputs / Outputs
Expansion Boards
I/O Matrix 4582 board
2
Refer to chapter "Current consumption" page 173 and the current calculation spread sheet.
3
Medium size enclosure 630H x 450W x 210D can be used to fit limited number of options. A combination of large and medium
size enclosures can be used if more options required. In 19" rack cabinets, a series of 19" face plates are also available.
4
Refer to G3 block wiring diagram, drawing no. F765
5
First input I0 cannot be used in NZ convention, only 3 programmable inputs are available.
6
Expansion boards are internally connected to COM loop 0, ensure total number of expansion boards and I/O matrix boards
connected to COM loop 0 does not exceed 6. Software 2.1.1 allows to use 6 x 4583.
7
Reduce the number of 4582 connected to COM loop 0 by one for every expansion board used.
8
If no expansion boards fitted, up to 24 fan control modules can be used i.e. 96 individual fans
Specifications
230VAC (176-264), 1.6A
24VDC @ 6.5A
Quiescent / alarm current is dependent on other equipment fitted
in FT1020G3, type and number of expansion boards, connected
external equipment, etc.
Operating 0 to + 40, Storage -40 to +70
Maximum 90, non-condensing
Standard cabinet 920H x 450W x 210D (with metal door closed)
1.5 Zinc anneal steel
Oyster, powder coated, ripple finish
AS7240.2, AS7240.4, AS4428.3:2010 and NZS4512:2010
Four COM loops (0-3), each loop can connect up to 255 devices
Four non-supervised inputs
Four programmable Supervised voltage outputs, 0.75 Amp each
Two programmable relay outputs, contact rating 2 Amp
4
Four programmable clean contact (N/O or N/C) inputs (I0-I3)
Two non-programmable relay outputs for ASE (fire & fault)
Six x 24V outputs for Web server, ASE, remote display units,
external applications 2-4 Amp.
Max. 6 of 4580, 4581 or 4583
Max. 24, 6 per COM loop if no expansion boards on Loop 0
Up to 6 modules can be used as zone or generic + 18 Fan control
modules (4 fans per module)
17
Technical/Programming Manual
FT1020G3 Rev 2.2.1
2
.
6
8
3
5
7
fitted.