Isolated alarm

An active fire alarm will automatically change state to "Isolated alarm" when the Bulgin key
(outside switch) is turned off, i.e. when it is not activated any more (see above).
The following is valid for an isolated alarm.
LEDs "Fire" (on the CIE front) not activated.
The CIE built-in buzzer not activated.
Presented as isolated alarm, see the example above (ISOLATED ......).
Programmable outputs will not be activated.
Output for routing equipment (Fire brigade TX) not activated.
146
Since this fault is always latched, it has to be acknowledged via menu H6.
).
FAULT: FB Silence switch active
The "
Any fire alarm "ALARM" and acknowledged alarm "ACKNOWLEDGED" will
automatically be disabled / isolated i.e. it has to be re-enabled via menu H2/
B1). Indicated by LED "General disablements" on the CIE front.
Any fire alarm "ALARM" and acknowledged alarm "ACKNOWLEDGED" will
automatically change the state to "Isolated alarm" (see below) and in the fire
alarm list (presented in the display), "ALARM" or " ACKNOWLEDGED " will
be replaced with "ISOLATED".
ISOLATED alarm
Zone
002-03
User definable alarm text for 002-03.
128
Technical/Programming Manual
FT1020G3 Rev 2.2.1
from activated to not activated
" will be Serviced.
Alarm number 1 (of 1)
Address
SMOKE