For more information, see chapter "Programmable outputs", page 79. The terminals
support a wire size up to 1.13 mm
5.3

Inputs and outputs expansion board 4583

Since the maximum current consumption for this type of boards can be up to 400 mA, only
two 4583 boards should be used however up to six boards can be configured (EBLWin
V2.1.1 or higher) with a warning if more than two are used when the SSD is validated in
EBLWin. Care must be taken to avoid overloading the fuse (F13) on the main board when
more than two boards are used.
Each board has to be programmed via EBLWin for Address (Board no.) set via the jumpers
"JP2-JP4", see Table 3, page 25.
The I/O expansion board 4583 has two programmable supervised / non-supervised voltage
outputs (Output 0-1), one special programmable output (Output 2) intended for German
extinguishing system and five programmable supervised / non-supervised inputs (Input 0-
4).
Connections to "J1:1-16" and "J2" according to drawing F731.
Output 0-1 has to be programmed via EBLWin for the following:
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Supervised / Non-supervised
Logic, i.e. normally low (default) or normally high (24V
Control expression (contains one or more trigger conditions)
One to five 33K resistors can be connected. When all connections are completed, perform
a "calibration of supervised output" via menu H5/A1. Calibration value has to be in the
range 4K7-50K.
supervised outputs (menu H5/A1)".
Voltage Output 0 (J1:1-2): Max. 200 mA (Fuse F1).
Voltage Output 1 (J1:5-6): Max. 200 mA (Fuse F2).
See chapter "Programmable outputs", page 79.
Output 2 has to be programmed via EBLWin for the following:
Type of output, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Logic, i.e. normally open (default) or normally closed.
Control expression (one or more trigger conditions)
Output 2 (J1:11-12): Normally Open (high resistance, 3K3) or Normally Closed (low
resistance, 680R). See drawing F731.
See also chapter "Programmable outputs", page 79.
Input 0-4 have to be programmed via EBLWin for the following:
Trigger condition (Triggered by)
A normally high output cannot be supervised. The supervision voltage is 1.5 – 3.6 V
31
resistors) and the polarity is reversed compared to activated output.
2
(1.2 mm).
31
See also the FT1020G3 Operation Manual chapter "Calibration of
28
Technical/Programming Manual
FT1020G3 Rev 2.2.1
22
)
.
DC
(depending on the number of supervision
DC