The three configuration options for the I/O matrix board are:
Generic, normally used for any special applications e.g. NZ index panel, mimic or
relay boards, pump status indications, etc. Maximum of six generic options can be
used, if no zone control is not used.
Fan Control, up to 6 fan modules can be used for each loop if no other applications
or expansion boards used. Four fans are the maximum number allowed per
module.
Zone Control, only six zone control options can be selected to provide a maximum
of 64 zones
There is no COM loop address to be set. Instead, the expansion board no. / address (0-
5) is set with jumpers (JP1-JP3) on the I/O Matrix board. See Table 3, page 25.
A total of up to 512 outputs can be used in FT1020G3, including all types of outputs.
The application board type can be selected via jumpers JP4-JP5 as shown in Table 5.

Table 5 I/O Matrix board 4582 type setting

Type (mode)
Application Board
Fan Control
Zone Control
33
Generic
Note: Jumper "JP6" is for future use
Each I/O Matrix board 4582 has to be programmed via EBLWin according to its
application.
Set the address on the 4582 via jumpers "JP1-JP3", see Table 3, page 25.
Right click on the respective Loop and select "Add I/O Matrix Board 4582" to bring
up the context menu to select the type of Application Board to be added as shown
below:
....and programmed for the following:
Address (must be the same board no. as set via jumpers "JP1-JP3").
Name (I/O Matrix Board # - normally not changed)
LED test on Input 15 (selected or not selected)
32
Due to the space limitation, only 12 zones are available in every zone control module
33
When SUB900 or SUB902 is used as a Generic application board, the Type of Inputs and Outputs can be customised by
programming in the EBLWin configuration software.
34
The new versions of NZ mimic boards SUB985, SUB986, SUB987 & SUB988 replace the discontinued SUB927 and SUB927R,
for more details refer to chapter "New mimic options" page 39
32
for each FT1020G3 system, if no generic options are used.
JP4
JP5
X
X
30
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Brooks Application
JP6
Board Part No.
SUB902
SUB900
SUB985-SUB988
34