NORMAL mode: The built-in short circuit isolator is in use. Programmed in
EBLWin as MCP type 4433 Flashing or non-flashing LED is set via EBLWin.
2330 mode: The built-in short circuit isolator is not in use. Programmed in
EBLWin as MCP type 3333
4439
Enclosed Addressable Manual Call Point
same as 3339 unit but it has built-in short circuit isolator. The isolator does not use
any COM loop address. The Address setting tool 3314 / 4414 is also used for mode
setting same as 4433.
For indoor use in premises where IP56 rating is required. Operating temp. -10 to
+55 °C.
Addressing and programming 4433/4439 with SCI
1. Connect the address setting tool to the MCP terminals SA and SB (without loop
connection).
2. Turn on the address setting tool then hold down both Write and Read buttons
simultaneously until "MODE: 0-3" appears.
3. Press "0" to select "M0 NORMAL" mode.
4. Enter the required technical address then press "write".
In EBLWin, select 4433/4439 from the "Obsoleted units" and add to the desired Loop.
Addressing and programming 4433/4439 without SCI
1. Connect the address setting tool to the MCP terminals SA and SB (without loop
connection).
2. Turn on the address setting tool then hold down both Write and Read buttons
simultaneously until "MODE: 0-3" appears.
3. Press "1" to select "M1 2330" mode.
4. Enter the desired technical address then press "write".
In EBLWin, select 3333/3339 from add loop unit and add to the desired Loop.
Notes:
1. Incorrect addressing mode or programming will cause the unit to report a "No reply
....." fault in the Control Unit.
2. When 4433 or 4439 is used in FT512 system, the MCP must be addressed in 2330
mode and programmed as 3333 / 3339.
3. The short circuit isolator feature in 4433 or 4439 can be used only in FT1020G3 or
FT128
9.1.1.3

Analogue Detectors

3308
Analogue heat detector. To be plugged in an Analogue base (3312 / 4313 / 3379).
Built-in LED is lit to indicate that the detector has activated a fire alarm. Prepared
for mechanical lock (screw attached) if required. The COM loop address is set with
the Address setting tool 3314 / 4414. The detector has an address label on which
the programmed COM loop address can be written.
The Address setting tool is also used for mode setting:
NORMAL mode: 3308 is set in this mode in EBLWin to one of three algorithms
(static response temp. range) for class:
48
When 4433/4439 is used as a replacement for 3333/3339, in EBLWin, 3333/3339 must be selected (not 4433 or 4439).
Technical/Programming Manual
48
. Flashing or non-flashing LED is set via EBLWin.
47
with isolator. Replaces 3339. 4439 is
55
FT1020G3 Rev 2.2.1