See also chapter "Programmable outputs", page 79.
4.6

Programmable inputs (I0-I3)

Connections according to drawing F732-02. Each input has to be programmed (via
EBLWin) for the following:
Type (trigger condition).
Logic, i.e. normally open (NO) or normally closed (NC) contacts.
Additional information when required, depending on the selected trigger condition
(Fault no., Zone, Address, Fault message (Error text), etc.)
Open = R > 20K. Closed = R < 500.
An input has to be activated > 0.5 sec.
See also chapter "Programmable inputs", page 72.
4.7

Relay outputs for routing equipment (TX)

Two dedicated non-programmable relay outputs are used for routing equipment. The
outputs can be tested via menu H1. For more information refer to the FT1020G3 Operation
Manual. Connections according to drawing F732-02.
4.7.1

Fire alarm output

This output is normally used for fire alarm routing equipment (Fire brigade TX). It is a
change-over relay contact that is activated when a fire alarm is generated in the system
De-activated output is (normally) indicated by the LED "Fire brigade TX"
When a specific zones or alarm points required to call the brigade, any programmable relay
can be used and type should be "Fire Brigade TX".
4.7.2

Fault condition output

This output is normally used for fault warning routing equipment (Fault TX). It is a change-
over relay contact that is normally activated and will be de-activated in case of a fault
the Control Unit (CIE)
Routing equipment "Fault TX activated".
23
The output can be disabled via "door open" (not recommended) or via menu H2/B5. See also chapter "Alert Annunciation",
page 115.
24
This output and programmable outputs with type of output = Fire brigade TX, will normally turn on the LED but a programmable
input with trigger condition = Activated routing equipment, can turn on the LED instead.
25
Also when the control unit is powered down (i.e. power supply and batteries are disconnected) or Watch-dog fault.
26
The output can be disabled via "door open" or via menu H2/B5.
26
. De-activated output (i.e. fault condition) is indicated by the LED
23