15.1.1

Interlocking output

The "Voltage Output" / "Relay Output" dialog boxes are used to configure the interlocking
output.
Type: "Interlocking" is to be selected.
Output signal period: Type Steady (continuous) or Type Steady delayed
activation is to be selected (checked by the "Validate" function in EBLWin).
Control Expression is to be programmed for the output, i.e. for the equipment to
be controlled.
Activated output will be indicated in menu H9/C1.
Name:
presentation number (Area-Point) could be added.
15.1.2

Interlocking input

The "Input" dialog box is used to configure the interlocking input.
Type "Interlocking" is to be selected.
Name:
presentation number (Area-Point) could be added.
Activated input will be indicated in menu H9/C1.
15.1.3

Interlocking combination

The interlocking function requires one interlocking output and one interlocking input to be
programmed in one interlocking combination.
Note: The interlocking outputs and inputs have to be programmed first before
programming the interlocking combination
An interlocking combination can have only an output or only an input programmed, e.g.
when a user definable text message is required to indicate an activated output or input and
alerted from the buzzer.
113
In the "Interlocking Combination" dialog box, all the outputs and inputs that have been programmed for interlocking are listed,
see Figure 35 next page.
It is recommended to add information, e.g.
It is recommended to add information, e.g.
97
Technical/Programming Manual
interlocking combination's
interlocking combination's
113
.
FT1020G3 Rev 2.2.1