9.1.5

Built-in Isolators

The units 4433, 4439 and 4477 have a built-in isolators that do not require any separate
COM loop addresses, only the Sequence Number, 00-63. As an option, these units can be
used without the isolator in function. If so, they have to be programmed in EBLWin as if
they were 3333, 3339 and 3377 units and via the Address setting tool 4413 set to 2330
mode instead of NORMAL mode.
9.1.6

Units for Hazardous (Ex) areas

In hazardous (Ex) areas, Intrinsically Safe (IS) and approved products are required. The
IS alarm points are connected to an interface outside the hazardous area.
Normally the Analogue addressable units, IS smoke (2840) and heat 2841 detectors are to
be used. They are connected to an IS barrier unit (2842), which is connected to a CIE via
a COM loop.
Conventional units are connected via a Galvanic isolator MTL 5061 (2820) to an expansion
board 4580 Ex zone line input. See also drawings F728 & F736.
9.1.6.1

Galvanic isolators / IS barrier units

MTL5061
intrinsically safe detectors and manual call points to an expansion board 4580 zone
line input (programmed in "Resistor-Ex" mode). The isolator has two zone line
inputs and two outputs (Channel 1 & 2) and is mounted in a Waterproof box
(IP66/67) which has to be mounted outside the hazardous (Ex) area,
compression glands for the cable entries and an End-Of-Line resistor (10K) with
an area >230 mm
mm. BASEEFA classification: EEx ia IIC T
2822 Isolated zone interface. The Isolated zone interface (2822) contains a waterproof
box (IP66/67) that is supplied with four compression glands for the cable entries,
an Isolated zone interface board (2823) mounted on a DIN rail, a DIN rail interface
intended for an I/O unit 3361 and one 8K2 EOL resistor. The box has to be
mounted outside the hazardous (Ex) area
A Galvanic isolator 2820 is to be connected to the Isolated zone interface 2822 (i.e.
to the Isolated zone interface board 2823), which is connected to a COM loop via
an Addressable multipurpose I/O unit 3361 that can be mounted inside the
waterproof box. (2820 and 3361 have to be ordered separately.) External power
supply 24 V
mm.
2842
Intrinsically safe (IS) barrier unit.
addressable IS detectors to a COM loop. The unit has connectors for COM loop
in / out, external power supply (24 V
of up to 20 IS detectors 2840 and 2841. It is mounted in a Waterproof box
(IP66/67). Five compression glands for the cable entries are supplied. Box
dimensions (L x W x H): 280 x 280 x 133 mm. DEKRA: II (1) G [Ex ia Ga] IIC.
9.1.6.2

Intrinsically Safe mounting bases

YBN-R / 4 IS Intrinsically Safe mounting base (2812). In the base, an intrinsically safe
conventional smoke or heat detector can be plugged. The base has terminals for
the zone line (in/out) and for an RIL.
Galvanic isolator (2820).
2
are supplied. Box dimensions (L x W x H): 175 x 125 x 150
(30 mA) is required. Box dimensions (L x W x H): 175 x 175 x 75
DC
Technical/Programming Manual
The isolator is used to connect conventional
=60°C.
amb
The barrier unit is used to connect analogue
, 60 mA) and one IS COM line for connection
DC
65
FT1020G3 Rev 2.2.1