Input Units - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

Notes:
3333/3339 can be used instead of 4433/4439 when the built-in short circuit isolator is not
to be used.
3377 can also be used instead of 4477 when the built-in short circuit isolator is not to be
used
Address setting
Each COM loop unit must have a unique COM loop address (001-255). This address and
the mode are set with an Address Setting Tool 3314 / 4414. Except otherwise stated, the
NORMAL mode is used in FT1020G3 (default). To set the detectors 440x in Advanced
Mode, the Address Setting Tool 4414 must be used.
9.1.1

Input units

Each COM loop input unit is added and programmed via EBLWin. Depending on type of
unit, the following to be programmed:
Technical address (COM loop address) 001-255
Name (normally not changed)
Zone number and Address within the zone
Alarm text (user definable)
Regular Alarm algorithm (some units only)
Options:
 Alternative Alarm algorithm & Time Channel (some units only)
 Alert annunciation & Time Channel (some units only)
 Disablement & Time Channel (some units only)
 Two-units-dependent fire alarm, i.e. co-incidence alarm & Time Channel (some
units only)
 Delayed (fire alarm)
 Quiet alarm
Technical/Programming Manual
53
FT1020G3 Rev 2.2.1