Class A1 Algorithm; Class A2 S Algorithm; Class B S Algorithm - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

is used to reduce nuisance alarms during working hours). The actual algorithm can be read
in menu H4/U4 or EBLWin.
When the CIE has picked up a sensor value above the fire alarm level (xx° C) for a
detector, the next two values from the same detector also have to be above the fire alarm
level to activate fire alarm in the CIE (This results in an approx. 5 seconds alarm delay).
The same is valid for pre-warning except it is a lower level (xx° C) value compared to fire
alarm. The Pre-warning option under EBLWin –System Properties can be either be enabled
or disabled.
The same is valid for heavy heat alarm except it is a higher level than for fire alarm.
The fire alarm, pre-warning and heavy heat alarm levels can be set in EBLWin collectively
for all detectors, see chapter "Alarm algorithms", page 153.
See FT1020G3 Operation Manual for more information.
17.5.1

Class A1 algorithm

Conforms to Class A1.
Typical / max application temperature 25 / 50° C.
Max. / min static response temperature 54 / 65° C.
The algorithm is as follows:
For a rate-of-rise < 4° C per minute:
Fire alarm level is 56° C.
Pre-warning level is 46° C.
Heavy heat alarm level is 90° C.
Rate-of-rise > 4° C per minute:
Fire alarm level is 46° C.
Pre-warning level is 36° C.
Heavy heat alarm level is 90° C.
The "Class A1 algorithm" will detect a fast temperature rise (rate-of-rise > 4° C per minute)
some minutes earlier than the "Class A2 algorithm".
17.5.2

Class A2 S algorithm

Conforms to Class A2 S.
Typical / max. application temperature 25 / 50° C.
Max. / min. static response temperature 54 / 70° C.
The algorithm is as follows:
Fire alarm level is 60° C).
Pre-warning level is 50° C.
Heavy heat alarm level is 90° C.
17.5.3

Class B S algorithm

Conforms to Class B S.
Typical / max. application temperature 40 / 50° C.
Max. / min. static response temperature 69 / 85° C.