Alarm Delay Time (Seconds); System Properties - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

automatically disabled in order to not activate a new fire alarm within 20 seconds. It will
stay disabled until re-enabled via menu H2/B1.
LED Fault / Disablements "General disablements" on the CIE front is indicating one or
more disablement in the system.
Note: According to the fire brigade standard AS4428.3:2010, the "Reset" button is not
effective unless the "Silence alarm" button is pressed first.
21.1.3.5

Alarm delay time (seconds)

Valid for the detectors and zone line inputs with this option selected via EBLWin.
30 is default, 0-255 seconds is possible.
Note:
The "Delayed" check box in EBLWin software V2.1.x for conventional zone line inputs
has changed to "AVF" in the AU and NZ conventions i.e. when ticked, the Alarm
Verification functions will be applied to the smoke detectors within this zone, see page
113.
The delay time for analogue detectors starts when the fire alarm normally should have
been activated and must be ≤ 30 seconds.
Or
The analogue smoke detectors activating fire alarm will activate an alarm device e.g. 3379
for the delay time period using the new trigger types, see chapter "
application
will go in full alarm condition, in this case the delay can be extended up to 255 seconds.
The function is added in EBLWin software ≥ V2.1.2.
21.1.4
System properties, Page 2
Fault Latching
faults, this is the default setting in the Australian convention.
Checkbox not marked, fault is non-latching i.e. Not corrected faults have to be
acknowledged but corrected faults will automatically be deleted from the fault list.
This option must be selected in the New Zealand convention.
Global reset of Fan Controls Outputs
i.e. all fan control systems in the FT1020G3 network system will be reset.
(Regarding Fan control, see page 31).
Checkbox not marked = Reset of fan control systems is local, i.e. all fan control
systems in the CIE where the switch is located will be reset.
Use Daylight Saving:
Australian convention: Forward 1 hour the first Sunday in October, 02:00  03:00.
Backward 1 hour the first Sunday in April, 03:00  02:00.
New Zealand convention: Forward 1 hour the last Sunday in September, 02:00 
03:00. Backward 1 hour the first Sunday in April, 03:00  02:00.
Checkbox not marked = Daylight saving time is not used.
Button "Silence alarm devices disables alarm devices":
should not be used in the Australian or New Zealand conventions, see page 127.
" page 113. If the smoke is not cleared within the delay time, the FT1020G3
(default): All faults have to be acknowledged as well as corrected
144
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Specific time delay
: Reset of fan control system is global,