28. Zone Line Input
Comments to the trigger conditions (above):
0. This trigger condition should be used in conjunction with a programmable COM
loop unit output in order to test / activate the output via this input. The output is
active as long as the input is active. This is valid even if the output is disabled.
1. "Activated Fault routing equipment" signal (feed-back) to FT1020G3 will light the
LED "Fault TX activated" on the front membrane. Output with trigger condition
"Indication Fault TX Activated" will be activated.
2. Activated Ventilation equipment feedback to the FT1020G3 Control Unit to light up
the LED "Ventilation".
3. Output with trigger condition "Activated Key cabinet" will be activated.
4. Activated Fire brigade TX feedback to the FT1020G3 Control Unit to light up the
LED "Fire brigade TX".
5. Key cabinet (for fire brigade) will activate a Key cabinet alarm. This feature is not
used in Australia or NZ due to different fire brigade requirements.
6. Alert annunciation, see chapter "Alert Annunciation", page 114 and FT1020G3
Operation Manual for more information.
7. Same as 6.
8. "Fire door closing" outputs will be activated for 20 seconds by this trigger condition.
NOTE: Only valid for inputs and outputs connected to the same CIE
9. Normally used for the New Zealand fire brigade Bulgin key switch "Evacuate".
When the switch is set to the evacuate position, the OWS or sounders will be active
until the switch restores to the normal position.
10. External fault will activate a fault in FT1020G3. A user definable fault message
("Error text") up to 40 characters will be shown.
11. External clock, timer, key switch, etc. can disable / re-enable alarm points. The
function Alert Annunciation can be set on / off by a time channel. Control outputs
can be turned on (activated) / off (de-activated) by a time channel.
12. Activated input will activate a fire alarm (Zone), e.g. a sprinkler zone alarm. This
trigger condition is normally used for a 3361 unit monitored Input 0 used as a Zone
line input (End-Of-Line capacitor) and as the type "Extinguishing".
13. Used to start a new "countdown", see 14 below.
Push button: NO, momentary action. One or more push buttons can be used.
14. Output for Extinguishing equipment (type of output = 2) has to have a delayed
activation programmed (a "countdown"). This "countdown" will be stopped when
an input with trigger condition 14 is activated. To start a new "countdown", see 13
above.
Push button info: NO, latching action. One or more push buttons can be used.
Manual reset of push button(s).
15. Activated input will generate a fault in FT1020G3. Output with trigger condition
"Extinguishing system fault" will be activated. The following fault message will be
shown:
79
Only valid for the Addressable multipurpose I/O unit 3361 input "In0", used as zone line input (Z).
80
One input activated in any control unit, will light up the LED in all control units.
81
One input activated in a control unit, will light up the LED in that control unit.
79
81
81
FAULT: Extinguishing system,
Control Unit xx
76
Technical/Programming Manual
FT1020G3 Rev 2.2.1