Fan Reset - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

Enhanced mode for independent configuration of Re0 and Re1
Enhanced mode for independent configuration of Re0 and Re1
Write the logical expression for Re0 and Re1 (enhanced mode only
Fault detection time is set to 30 seconds by default, change time if required.
Select Re0 and/or Re1 type "Fire ventilation" (default).
If a supply air fan is to be configured, on the "Output signal period" on Re0 and/or
Re1 dropdown menu select "Supply Air Fan" as shown in step 7.
7. For supply air fan applications, set the post timing required to reset the duct detector
as follow:
On the "System" tab, select "Output signal period".
In the displayed dialog box shown below, select one of the "Undefined" options
Re-name the "Undefined" to Supply Air Fan or any other name then click edit as
shown below.
On the drop down menu, select "Steady, delayed de-activation"
In the de-activation box, enter 75, this will set the post timing of the duct smoke
detector to 60 seconds i.e. the duct detector will reset after 60 seconds of clearing
up the smoke.
Click ok.
6.1.4

Fan Reset

A fan reset button is added to the front display of the fan control module to comply with the
requirements of AS1668.2 and used to independently reset 3361 relays Re0 and Re1 in
fire mode conditions. The two relays should be programmed in EBLWin to be "Latched" i.e.
resetting the alarm in the CIE will not bring the fans to the non-fire mode condition until the
reset button is pressed. If the alarm remains active in the CIE, the fan reset button will not
function. The fan reset function can be selected in EBLWin to be either local reset or global
(Default) reset.
To change this setting in EBLWin select, System I Properties which will bring up the System
Properties dialog box then select the "Page 2" tap. Check/uncheck the box against "Global
Reset of Fan Control Outputs" accordingly
36
In non-enhanced mode, if Re0 is normally open, Re1 will automatically be normally closed and vice versa. If "Enhanced fan
control" function is selected, Re0 and Re1 tabs will be available for individual programming.
37
In non-enhanced mode, if Re0 is normally open, Re1 will automatically be normally closed and vice versa. If "Enhanced fan
control" function is selected, Re0 and Re1 tabs will be available for individual programming.
38
In non-enhanced mode, only Re0 requires logical expression hence Re1 will f ollow same logical expression.