New or modified features in EBLWin only

Fault latching in the Australian convention is set as default in system properties.
If the CIE time differs more than 60 minutes to the time shown in the PC, a dialog
box will display when logon is performed. Via this dialog box, the PC time can be
used to update the CIE time.
A user that is defined to have access to Web-server (not the CIE) can have a
password containing between 6 and 10 character (not only digits).
If a Single TLON network (no redundancy) is configured, the validation check will
generate a warning "Convention violation".
In V2.2.0, the fault list can be sorted by CIE and COM loop.
32.2.3

New or modified feature in system software EBL only

Output without a control expression are considered to be non-existent in the
system. In previous versions, an output with no control expression could be
manually controlled from the menu system, fan control or via EBLnet. In V2.2.0, an
output with no control expression is considered to be non-existent and cannot be
controlled in any way.
If an output is to be controlled manually only, it must have a never-true control
expression similar to "TimeChannelActivated" (Always off).
If an input is set to "Not used", or if an output has no control expression, the
supervision fault is not generated even if the "Supervised" check box in EBLWin is
checked.
Technical/Programming Manual