5.4

Addressable COM Loop Display Modules

The ancillary 3U rack is designed to be fitted with any combination of display modules as
shown in Figure 12 below.
Any combination of modules in Figure 13 to Figure 16 will fit onto the 3U Ancillary Modules
Face Plate shown in Figure 12 These provide maximum flexibility for controlling and
indicating of programmable inputs and outputs when used with FT1020G3 Addressable
FDCIE loaded with software ≥ V2.4.x.
Note: Modules with separate I/O matrix 4582 can be used with software prior to V2.4 whilst
modules with built-in I/O matrix circuit e.g. 1205/1206/1211 must be used with software ≥
V2.4.x . Other modules 1204, 1207, 1208, 1209 and 1210 must use ≥ V2.4.x.
Total capacity of a single 3U 19" rack is 420mm, first 20mm is always allocated for power
monitor module. The other 400mm can be used to mount multiple different modules. Some
modules require 1 space (50mm), others require 2 spaces (100mm). Blank modules are
also available to fill up the gaps for any unused modules in the rack.
All modules follow a similar pattern and are designed to be mounted on the 19" metal 3U
plate and secured by suitable hardware. A rectangular washer (PCB) is used to help retain
the adjacent module. The modules are interconnected by a single ribbon cable part number
CA380. A blank module 10HP (50mm) is used to cover an unused module space. Also
available is a Blank Module 4HP (20mm) used to blank out the space reserved for the 1204
Power Monitor Module when 3U Ancillary Modules are used.
The new display modules are versatile and interchangeable modules allowing for quick and
easy installation and configuration as shown in Figure 12. The modules are mounted from
the rear of the ancillary rack using supplied prolong washer (or small PCB) and fasteners.
The functions and features of the new display modules are shown in Table 12 below.

Table 12 Module specifications

Module
Description
No.
1204
Power Monitor Module
1205
15 Zone Control Module
1206
4 Fan Control Module
8 Key / 8 LED Control and
1207
Display Module
4 Key / 8 LED Control
1208
and Display Module
1209
8 LED Display Module
6 LED Pump Status
1210
Display Module
4 Damper Control
1211
Module

Figure 12 3U Ancillary Modules Face Plate

Inputs to
FDCIE
24V and 5V power
Poll, 24V OK, 5V OK
fail
Disable, Fault and Alarm
Disable zone
LED
Fire Mode, Run, Stop,
On, Auto, OFF
Fault, Phase
Fault, On, Auto, Off
8 programmable
8 Programmable LED's
Switches (input)
(output)
4 programmable
8 Programmable LED's
Switches (input)
(output)
8 Programmable LED's
N/A
(output)
6 x Programmable LED's
N/A
(output)
Fire Mode, Fire, Non-Fire,
Fire, Auto,
Fault, Power Fault, Fire,
Non- Fire
Auto, Non-Fire
33
Operation Manual
FT1020G3 Rev 2.10.4
No. of
Indicators
Add.
1
1
1
2
2
1
1
1
Module
space
20 mm
100 mm
100 mm
50 mm
50 mm
50 mm
50 mm
100 mm