Zones Expansion Board 4580; Type Of Zone Line Input; Table 3 Expansion Boards Address (Jumpers) Setting - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

Table 3 Expansion boards address (jumpers) setting

Board no.
(address)
0
1
2
3
4
5
6
7
X=Shunted, Blank = Open
Address 6 & 7 are not currently used
5.1

8 zones expansion board 4580

Each board has to be programmed via EBLWin with an address (Board no.) which is set
via the jumpers "JP2-JP4", see Table 3 above.
The 4580 board has eight conventional zone line inputs (0-7) intended for conventional
detectors, MCP, flow switch input or any N/O clean contact. The end-of line device must
be connected in the last alarm point on each zone, depending on the selected "Type of
zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing F728.
Each zone line input has to be programmed via EBLWin for the following:
Type of zone line input (see below), depending on detectors / end-of-line device
(capacitor or resistor), i.e. different threshold levels etc.
Alarm at short circuit i.e. whether a short- circuit on the zone line input generates
a fault or a fire alarm.
Zone number (address optional)
AVF (Alarm Verification Facility), if required
Text (Alarm / fault text when required)
Alert annunciation time channel
Disable time channel
Two-unit dependency time channel
Type of detectors connected to the zone line input (see "Fire alarm type A and Fire
alarm type B" page 118 for an explanation of A and B)
The terminals support a wire size up to 1.13 mm
5.1.1

Type of zone line input

Each input must be selected either as "Not used" or as one of the following types / modes.
4580, 4581 and 4583
JP2
JP3
JP4
X
X
X
X
X
X
X
25
Technical/Programming Manual
FT1020G3 Rev 2.2.1
4582
JP1
JP2
X
X
X
X
X
2
(1.2 mm).
JP3
X
X