17.16.1

Disable / Re-enable zone

A whole zone (all addressable alarm points within a zone, including the manual call points)
can be disabled via menu H2/B1 or via the zone control front buttons (if fitted). This menu
is also used to disable a conventional zone, i.e. a 3361 unit's zone line input (Z) and
expansion board 4580 zone line inputs. Re-enable via menu H2/B4 or automatic re-
enabling at a specified time.
17.16.2

Disable / Re-enable zone - address

Individual alarm points (zone-address) can be disabled and re-enabled via menu H2/B1.
A time channels can instead be used to disable and re-enable automatically.Disable / Re-
enable control output
All outputs (except outputs of type "Alarm Device") can be individually disabled and re-
enabled via menu H2/B2. Disabled output will stay in (or return to) the normal condition for
the output respectively.
17.16.3

Disable / Re-enable output type

The control outputs can be collectively disabled via menu H2/B3, type:
"Control (general)"
"Extinguishing"
"Ventilation"
"Interlocking"
It is possible to do this for one or more specific Control Units or for all Control Units (i.e. the
whole system). Re-enabled via menu H2/B3. Disabled outputs will stay in (or return to) the
normal condition for the output respectively.
17.16.4

Disable / Re-enable alarm devices

The control outputs of type "Alarm device" (OWS) can be collectively disabled via menu
H2/B4. It is only possible to do this for all Control Units (i.e. the entire system). Disabled
outputs will stay in (or return to) the normal condition for the output respectively.
17.16.5

Disable / Re-enable interlocking output

The type "Interlocking output" can be individually disabled and re-enabled via menu H9/C3.
See also chapter "Disable / re-enable interlocking output (H9/C3)", page 100.
17.16.6

Disable / Re-enable outputs for routing equipment

The control outputs of type "Routing equipment (Fire brigade TX and Fault TX)" can be
Disabled and Re-enabled via menu H2/B5. For more information see FT1020G3 Operation
Manual.
17.16.7

Disable / Re-enable alert annunciation function

The alert annunciation function can be disabled / re-enabled via menu H2/B6. Disabled
alert annunciation function will be disabled until Re-enabled. Refer to FT1020G3 Operation
Manual.
17.16.8
Disconnect & Re-connect loop / zone line input
The following can be d
COM loop
isconnected and re-connected via menu H8/S1:
120