For each level, an output control expression and a sound type is programmed (via
EBLWin). For more technical data, see the product datasheet.
The COM loop address is set with the Address setting tool 3314 / 4414 which is
also used for mode setting.
NORMAL mode: 4477 with the built-in isolator in use.
2330 mode: 4477 with the built-in isolator not in use. 4477 replaces a 3377 unit.
Note: See also Table 2 "Control Panel Limitation", page 18.
3379
Addressable sounder base.
together with a sounder. 3379 is mounted in the ceiling. An Analogue detector can
be plugged in the base, which has screw terminals for the COM loop and a remote
indicator (RIL). Prepared for mechanical lock of the detector - if required. Recess
for label holder (3391). 3379 is COM loop powered, i.e. the number of sounder
bases is dependent on the type and number of other units connected to the COM
loop
Three sound types
For each level, an output control expression and a sound type is programmed (via
EBLWin). High sound output (approx. 4.5 dB higher) can be selected via EBLWin
(more current will be required). For more technical data, see the Product datasheet.
The COM loop address is set with the Address setting tool 3314 / 4414. The unit
has an address label on which the programmed COM loop address can be written.
(The detector has its own COM loop address set via the Address setting tool).
The Address setting tool 3314 / 4414 is also used for mode setting:
NORMAL mode: Used for 3379 in system FT1020G3.
Note: See also Table 2 "Control Panel Limitation", page 18.
4380
Addressable beacon.
via the COM loop, i.e. the number of beacons is dependent on the type and number
of other units connected to the COM loop but max. 10 per COM loop. Red ABS
plastic housing and PC lens. The light output is 1 Cd and the flash rate is 1 Hz. An
output control expression is programmed (via EBLWin). For more technical data,
see the Product Leaflet.
The COM loop address is set with the Address setting tool 3314/4414. The beacon
has an address label on which the programmed address can be written.
The Address setting tool 3314 / 4414 is also used for mode setting:
NORMAL mode: Used for 4380 in system FT1020G3.
66
This unit has replaced the Sounder base 3378.
67
High tone can be selected via EBLWin V2.1.x and higher, more current will be required.
The addressable beacon is discontinued and will be replaced by new VAD's
68
Alternating (two-tone) 990 / 650 Hz, 0.25s / 0.25s (2 Hz)
66
65
.
67
(tones)
Steady (continuous) 3650 Hz
Intermittent (pulsed) 3650 Hz, 0.5s / 0.5s (1 Hz)
Intermittent (pulsed) 3650 Hz, 0.167s / 0.167s (3 Hz)
68
The LED beacon is connected to a COM loop. It is powered
Technical/Programming Manual
3379 consists of an Analogue base (3312) mounted
and three priority levels are available:
63
FT1020G3 Rev 2.2.1