Configuration And Programming; Figure 15 Mimic Board Options - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

Master LED mimic board SUB985
Master Terminal mimic board SUB987
Note: Mounting holes of the new series of mimic boards are slightly different to the
mounting holes of the previous version (SUB927) i.e. new mimic LED boards must be
used in the new index cabinets.
6.3.3

Configuration and programming

The following procedures are used to configure the NZ mimic or index panel:
1. Select a COM loop then "Add I/O matrix board 4582" and select "Add generic". The
following dialog box will appear:
2. Enter the generic address (0-5) (usually automatically assigned) in the general
information area and give it an application name e.g. NZ Index panel.
3. Select the check box "LED test on Input 15" if this button is to be used for LED test
or uncheck the box if not required.
4. Right click on the Generic Board (i.e. NZ Index
Panel as a given example) that was added in step
1 and choose
as required (0-47) and enter the fields in the
Slave LED mimic board SUB986
Slave terminal mimic board SUB988

Figure 15 Mimic Board Options

from the context menu
40
Technical/Programming Manual
FT1020G3 Rev 2.2.1