Zone Control Configuration; Figure 14 Zone Control Connection - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

Disabled LED (Amber) – Illuminates when a zone is disabled either by the disable switch
on the zone control card or where the zone is disabled via menu H2/B1.
Disable Switch –Pressing the disable switch will disable the specific zone selected.
Pressing the switch a second time will re-enable the zone. Functions are the same as menu
H2/B1.
LED Test Switch – Pressing the LED test switch illuminates all indicators, if Input 15" is
selected when programming the zone control function.
6.2.2

Zone Control Configuration

When the I/O Matrix board is selected in EBLWin to "Zone Control" type, up to 16 zones
[0-15] can be configured. The display Board is limited to only 12 zones and one additional
switch for LED test. The following procedures are used to configure the zone control
module:
1. Right click on a COM loop and "Add I/O matrix board 4582" then select "Add zone
control". The following dialog box will be showing.
24VDC
I/O Matrix Board
4582
Zone Control & indicating board
SUB900
ZONE CONTROL
AL
AL
Disable
DS
Disable
DS
Disable
FT
FT
AL
AL
Disable
DS
Disable
DS
Disable
FT
FT
AL
AL
Disable
Disable
Disable
DS
DS
FT
FT

Figure 14 Zone Control Connection

38
Technical/Programming Manual
FT1020G3 Rev 2.2.1
COM Loop
Or 24VDC from
external source
AL
AL
DS
Disable
DS
FT
FT
AL
AL
DS
Disable
DS
FT
FT
AL
AL
Disable
DS
DS
FT
FT
LED